Lakewood, Colorado
Opus Architects & Engineers
LEED® Silver

This project is a three-story, 128,300 sf office building built by Opus Northwest for the Federal Department of Transportation.

Completed in July 2004, the facility has achieved LEED Silver Certification by the U.S. Green Building Council, receiving a total of 35 points. The Weidt Group's work was supported in part by Xcel Energy, and additional analysis was completed for Opus to support the LEED decision making process. The energy outcomes are 47% better than code and 34% better than LEED baseline.

Key Strategies
  • Low-E bronze tinted glass in the lower windows of a thermally broken aluminum frame
  • Low-E clear high visible transmittance glass in the upper windows of a thermally broken aluminum frame
  • R-30 roof insulation; R-19 wall insulation
  • Occupancy sensor control of lighting in various spaces
  • Direct/indirect lighting systems at 45 fc with an 85% reflective ceiling and High Performance T8 lamps and a 0.74 ballast factor
  • Open offices 0.67 - 0.87 w/sf
  • Private offices 1.13 - 1.33 w/sf
  • Conference rooms 1.30 - 1.50 w/sf
  • Dimming daylighting control of lighting in open offices
  • Water-cooled chiller at 0.52 kw/ton (actual operating conditions) with VFD on chiller compressor
  • Variable frequency drive on the cooling tower fan
  • 96% efficient gas boiler with 10:1 turndown ratio
  • Variable frequency drives on fans and pumps
  • CO2 control of outside air
  • CO control of the garage ventilation fan
  • 83% efficient domestic hot water heater
  • Premium efficiency supply/return fan and pump motors
  • High-efficiency low voltage transformers